华为SUN2000-375W-USP0智能光伏优化器用户手册说明书

华为SUN2000-375W-USP0智能光伏优化器用户手册说明书


2024年2月15日发(作者:华为即将发布的新品)

SUN2000-375W-USP0 Smart PV Optimizer

User Manual

Issue

Date

04

2019-07-05

HUAWEI TECHNOLOGIES CO., LTD.

Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved.

No part of this document may be reproduced or transmitted in any form or by any means without prior

written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.

All other trademarks and trade names mentioned in this document are the property of their respective

holders.

Notice

The purchased products, services and features are stipulated by the contract made between Huawei and

the customer. All or part of the products, services and features described in this document may not be

within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,

information, and recommendations in this document are provided "AS IS" without warranties, guarantees or

representations of any kind, either express or implied.

The information in this document is subject to change without notice. Every effort has been made in the

preparation of this document to ensure accuracy of the contents, but all statements, information, and

recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.

Address: Huawei Industrial Base

Bantian, Longgang

Shenzhen 518129

People's Republic of China

Website:

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. i

SUN2000-375W-USP0 Smart PV Optimizer

User Manual About This Document

About This Document

Purpose

This document describes the SUN2000-375W-USP0 smart photovoltaic (PV) optimizer in

terms of its functions, electrical properties, and structure.

Figures provided in this document are for reference only.

Intended Audience

This document is intended for:

Sales engineers

Technical support engineers

Maintenance engineers

Symbol Conventions

The symbols that may be found in this document are defined as follows.

Symbol

Description

Indicates an imminently hazardous situation which, if

not avoided, will result in death or serious injury.

Indicates a potentially hazardous situation which, if not

avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not

avoided, may result in minor or moderate injury.

Indicates a potentially hazardous situation which, if not

avoided, could result in equipment damage, data loss,

performance deterioration, or unanticipated results.

NOTICE is used to address practices not related to

personal injury.

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. ii

SUN2000-375W-USP0 Smart PV Optimizer

User Manual About This Document

Symbol

Description

Calls attention to important information, best practices

and tips.

NOTE is used to address information not related to

personal injury, equipment damage, and environment

deterioration.

Change History

Changes between document issues are cumulative. The latest document issue contains all

updates made in previous issues.

Issue 04 (2019-07-05)

Updated A Technical Specifications

Issue 03 (2018-08-08)

Updated 1 Safety Precautions

Issue 02 (2018-03-23)

Modified all structural diagrams in the document.

Issue 01 (2018-01-02)

This issue is the first official release.

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. iii

SUN2000-375W-USP0 Smart PV Optimizer

User Manual Contents

Contents

About This Document .................................................................................................................... ii

1 Safety Precautions ......................................................................................................................... 1

2 Overview ......................................................................................................................................... 4

2.1 Product Overview ......................................................................................................................................................... 4

2.2 4

2.3 Application Scenario ..................................................................................................................................................... 5

2.4 Model Naming Conventions ......................................................................................................................................... 6

2.5 Product Structure .......................................................................................................................................................... 6

3 8

3.1 Troubleshooting ............................................................................................................................................................ 8

3.2 Replacing a Optimizer .................................................................................................................................................. 9

A Technical Specifications ........................................................................................................... 10

B Acronyms and Abbreviations .................................................................................................. 15

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. iv

SUN2000-375W-USP0 Smart PV Optimizer

User Manual 1 Safety Precautions

1

General Safety

Safety Precautions

Follow the precautions and special safety instructions provided by Huawei when

operating this product. Personnel who plan to install or maintain Huawei devices must

receive a thorough training, understand all necessary safety precautions, and be able to

correctly perform all operations. Huawei will not be liable for any consequences that are

caused by the violation of general safety regulations and device usage safety standards.

Before performing operations, read through this manual and follow all the precautions to

prevent accidents. The "DANGER", "WARNING", "CAUTION", and "NOTICE"

statements in this document do not represent all the safety instructions. They are only

supplements to the safety instructions.

Operation personnel should comply with local laws and regulations. The safety

instructions in this document are only supplements to local laws and regulations.

Do not operate the product or handle cables during thunderstorms.

Before operating the product, remove any conductors such as jewelry or watches.

Use insulated tools during operations.

Bolts should be tightened with a torque wrench and marked using red or blue color.

Installation personnel should mark tightened bolts in blue. Quality inspection personnel

should confirm if the bolts are tightened and then mark them in red. If screws or bolts

used to secure the device are not tightened to the required torque, the device may fall

from the mounting bracket.

Follow specified procedures during installation and maintenance. Do not attempt to alter

the device or deviate from the recommended installation procedures without prior

consent from the manufacturer.

Install the product in strict accordance with the quick guide.

If the optimizer needs to mounted onto a PV module frame, use the

TSM-XXXDD05A(II), TSMXXXDD05A.05(II), TSM-XXXDD05A.08(II), or

TSM-xxxPD05.50 series PV modules from Trina Solar Co., Ltd.

If the optimizer needs to be mounted onto a PV module support, ensure that the opening

width of the support is 10.5–14.0 mm and the thickness is 3–7 mm.

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS - This manual contains important instructions for Models

SUN2000-375W-USP0 that shall be followed during installation and maintenance of the

optimizer.

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 1

SUN2000-375W-USP0 Smart PV Optimizer

User Manual 1 Safety Precautions

Disclaimer

Huawei shall not be liable for any consequence caused by any of the following events:

Transportation damage

The storage conditions do not meet the requirements specified in this document.

Incorrect installation or use

Installation or use by unqualified personnel

Failure to obey the operation instructions and safety precautions in this document

Operation in extreme environments which are not covered in this document

The optimizer operates beyond specified ranges.

Unauthorized modifications to the product or software code or removal of the product

Device damage due to force majeure (such as fire, and storm)

The warranty expires and the warranty service is not extended

Installation or use in environments which are not specified in related international

standards

Personnel Requirements

Only certified electricians areallowed to install, connect cables for, maintain, troubleshoot,

andreplace the optimizer.

Operation personnel should receive professional training.

Operation personnel should read through this document and follow all the precautions.

Operation personnel should be familiar with the safety specifications about the electrical

system.

Operation personnel should understand the composition and working principles of the

grid-tied PV power system and local regulations.

Operation personnel must wear proper personal protective equipment (PPE).

Protect Labels

Do notscrawl or damage any warning labels on the optimizer because theselabels contain

important information about safe operation.

Do notscrawl or damage the nameplate on the back of the optimizer becauseit contains

important product information.

Installation

Ensurethat the optimizer is not connected to a power supply or powered onbefore

finishing installation.

To allowproper heat dissipation and installation, maintain appropriate clearancesbetween

the optimizer and other objects.

Electrical Connections

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 2

SUN2000-375W-USP0 Smart PV Optimizer

User Manual 1 Safety Precautions

Before connecting cables, ensure that the optimizer is not damagedin any way. Otherwise,

electric shocks or fire may occur.

Ensure that all electrical connections comply with local electrical standards.

Ensure that the cables used in a grid-tied PV system are properly connected and insulated

and meet all specification requirements.

The output wiring terminals of the optimizer cannot be hot swapped. If the terminals are

hot swapped, the optimizer may be damaged.

Operation

High voltagemay cause an electric shock, which results in serious injury, death,or serious

property damage from the optimizer in operation. Strictlycomply with the safety precautions

in this document and associateddocuments when operating the optimizer.

Donot touch an energized optimizer because it has a high temperature.

Follow local laws and regulations when operating the device.

Maintenance and Replacement

High voltage may cause an electric shock, which results in seriousinjury, death, or serious

property damage from the optimizer in ore, before maintenance, power off

the optimizer and strictlycomply with the safety precautions in this document and

associateddocuments to operate the optimizer.

Maintain the optimizer with sufficient knowledge of this document and propertools and

testing devices.

Temporary warning signs or fences must be placed to prevent unauthorized people from

entering the site.

The optimizer can be powered on only after all faults are rectified. Failingto do so may

escalate faults or damage the device.

During the maintenance, observe ESD precautions and wear ESD gloves.

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 3

SUN2000-375W-USP0 Smart PV Optimizer

User Manual 2 Overview

2

2.1 Product Overview

Figure 2-1 Optimizer

Overview

The optimizer is a DC-DC converter installed on the back of PV modules in a PV system. It

tracks the maximum power point (MPP) of each PV module to improve the energy yield of

the PV system, and performs the functions of module-level shutdown, module-level

monitoring, and automatic positioning.

2.2 Working Principles

Conceptual Diagram

The input port of the optimizer connects to the PV module. Through a DC/DC circuit, the PV

input voltage is converted into a required voltage and the maximum power point tracking

(MPPT) function is implemented.

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 4

SUN2000-375W-USP0 Smart PV Optimizer

User Manual 2 Overview

Figure 2-2 Conceptual diagram

Functions

Module-level MPPT: The optimizer improves the energy yield of the PV system by

continuously tracking the MPP of each PV module.

Module-level shutdown: The optimizer cuts off the voltage of each PV module.

Module-level monitoring: The optimizer monitors the operating status of each PV

module.

Automatic physical positioning: The optimizer determines the PV module location by

automatic physical positioning.

2.3 Application Scenario

The optimizer is mandatory and used for all PV modules. It performs the functions of MPPT,

module-level shutdown, monitoring, and automatic positioning.

Figure 2-3 Application scenario

(1) Inverter

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 5

SUN2000-375W-USP0 Smart PV Optimizer

User Manual

The inverter icon is for reference only.

2 Overview

2.4 Model Naming Conventions

Figure 2-4 Model naming conventions

2.5 Product Structure

Figure 2-5 Ports

(1) Output port (positive)

(3) Input port (negative)

(2) Output port (negative)

(4) Input port (positive)

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 6

SUN2000-375W-USP0 Smart PV Optimizer

User Manual 2 Overview

Figure 2-6 Dimensions

(1) Mounting ear

Table 2-1 Label description

Label

Burn warning

Name

Electric shock warning

Direct current

Label Name

Grounding

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 7

SUN2000-375W-USP0 Smart PV Optimizer

User Manual 3 System Maintenance

3

3.1 Troubleshooting

Alarm Name

Input overvoltage

Possible Cause

Overtemperature

System Maintenance

Table 3-1 Common alarms and troubleshooting measures

Troubleshooting Suggestion

The PV module output

1. Check whether the open-circuit

voltage of the PV modules connected

voltage exceeds the

to the SUN2000P exceeds 80 V.

maximum input voltage

of the SUN2000P. 2. Check whether the PV modules are

connected in series.

1. Check the ventilation and ambient

The ambient

temperature at the SUN2000P

temperature exceeds the

installation position. If the ventilation

upper threshold or the

is poor or the ambient temperature

SUN2000P is not

exceeds the upper threshold, improve

installed as required.

the ventilation and heat dissipation.

2. If the ventilation and ambient

temperature are normal, contact the

installation contractor.

A short circuit occurs

on the output of the

SUN2000P.

1. Check whether the inverter works

properly. If not, rectify the fault first.

2. Check that the output cable of the

SUN2000P is connected correctly.

3. Power off the system. Disconnect

cables on the input and output sides of

the SUN2000P after 5 minutes.

Reconnect them after 1 minute and

then power on the system. If the fault

persists, contact the installation

contractor.

Power off the system. Disconnect cables

on the input and output sides of the

SUN2000P after 5 minutes. Reconnect

them after 1 minute and then power on

the system. If the fault persists, contact

the installation contractor.

Output short circuit

Internal hardware

fault

The SUN2000P is not

properly installed or is

faulty.

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 8

SUN2000-375W-USP0 Smart PV Optimizer

User Manual 3 System Maintenance

Contact the installation vendor if all failure analysis procedures listed above are completed and the fault

still exists.

3.2 Replacing a Optimizer

Prerequisites

The protective gloves and socket wrench are available.

A new optimizer is available.

Procedure

Step 1 Put on the protective gloves.

Step 2 Power off the inverter.

Step 3 Disconnect the input terminal of the optimizer.

Step 4 Remove the faulty optimizer.

1. Record the cable connection positions on the optimizer and disconnect the cables.

2. Unscrew the optimizer.

Step 5 Install the new optimizer.

1. Secure the new optimizer to the appropriate position, and tighten the bolt.

2. Connect the cables to the new optimizer based on the recorded information.

Step 6 Power on the inverter.

Step 7 Take off the protective gloves.

----End

Follow-up Procedure

Pack the faulty component and send it to the local Huawei warehouse.

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 9

SUN2000-375W-USP0 Smart PV Optimizer

User Manual A Technical Specifications

A

Environmental Specifications

Item

Operating temperature

Storage temperature

Relative humidity

Altitude

Technical Specifications

Table A-1 Environmental specifications

Specifications

–40°C to +85°C

–40°C to +85°C

0%–100% RH

0–4000 m

(When the altitude ranges from 2000 m to 4000 m, the

ambient temperature decreases by 0.7°C for each

additional 100 m.)

Electrical Specifications

Table A-2 Electrical specifications

Item

DC input

Specifications

Input voltage

Maximum input current

Maximum input power

DC output Output voltage range

Maximum output current

Efficiency

DC input

protection

Maximum efficiency

Input overvoltage protection threshold

Input overvoltage recovery threshold

10–80 V DC

12 A

375 W

4–80 V DC

15 A

99.5%

82–87 V DC

81–86 V DC

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 10

SUN2000-375W-USP0 Smart PV Optimizer

User Manual A Technical Specifications

Item Specifications

Input undervoltage protection threshold

Input undervoltage recovery threshold

7–9 V DC

8–10 V DC

85–90 V DC

Supported

3 million hours (Telcordia

SR-332 Method 1)

25 years

DC output

protection

Reliability

requirements

Protection

level

Safety

design

Output overvoltage protection threshold

Output overcurrent protection

Mean time between failures (MTBF)

Design life

NEMA TYPE 6P

UL1741

Figure A-2 Iin_max-Ta relationship curve

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 11

SUN2000-375W-USP0 Smart PV Optimizer

User Manual A Technical Specifications

Figure A-3 Pin_max-Ta relationship curve

Figure A-4 Pin_max-Vin relationship curve

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 12

SUN2000-375W-USP0 Smart PV Optimizer

User Manual A Technical Specifications

Figure A-5 Iin_max-Pin relationship curve (65°C)

Figure A-6 Iin_max-Pin relationship curve (85°C)

EMC Specifications

Table A-3 EMC specifications

Item

Electromagnetic

interference (EMI)

Specifications

Radiated emission (RE) FCC Part 15 Class B

ICES 003

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 13

SUN2000-375W-USP0 Smart PV Optimizer

User Manual A Technical Specifications

Item

Electromagnetic

susceptibility (EMS)

Specifications

ESD IEC61000-4-2

Contact discharge: ±6 kV,

criterion B

Air discharge: ±8 kV,

criterion B

Electrical fast transient (EFT)

Radiated susceptibility (RS)

Conducted susceptibility (CS)

Surge susceptibility

IEC61000-4-4, ±2 kV,

criterion B

IEC61000-4-3, criterion A

10 V/m field strength

IEC61000-4-6, criterion A

Power port: 10 V

IEC61000-4-5

Common mode: 2 kV

Structural Specifications

Table A-4 Structural specifications

Item

Installation mode

Dimensions (H x W

x D)

Specifications

Hung on a PV module support or PV module frame

3.35 in. x 5.31 in. x 0.99 in. (85 mm x 135 mm x 25.2 mm)±0.02

in. (0.5 mm), excluding the mounting ears and waterproof

terminals)

5.90 in. x 5.31 in. x 0.99 in. (150 mm x 135 mm x 25.2

mm)±0.02 in. (0.5 mm), including the mounting ears and

waterproof terminals)

Net weight 0.75 kg

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 14

SUN2000-375W-USP0 Smart PV Optimizer

User Manual B Acronyms and Abbreviations

B

D

DC

E

EFT

EMI

EMS

ESD

M

MPPT

R

RE

RS

Acronyms and Abbreviations

direct current

electrical fast transient

electromagnetic interference

electromagnetic susceptibility

electrostatic discharge

maximum power point tracking

radiated emission

radiated susceptibility

Issue 04 (2019-07-05) Copyright © Huawei Technologies Co., Ltd. 15


发布者:admin,转转请注明出处:http://www.yc00.com/num/1707957394a1532642.html

相关推荐

发表回复

评论列表(0条)

  • 暂无评论

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:admin@example.com

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信